In This Section:
Superior EMD D3512B Halberstadt Taurus60 Autres
|


GENERATOR:
STEWART & STEVENSON MODEL 2416G-2000
2387 KW, 60 HZ, 2000 KW, 50 HZ
3000 KVA, 60 HZ, 2500 KVA, 50 HZ
1200 RPM, 60 HZ, 1000 RPM , 50 HZ
13,200 at 60 HZ , 11000 VOLTS 50 HZ
3 PHASE
WYE CONNECTED
80 DEG. C TEMP. RISE
40 DEG. C AMBIENT TEMP.
CLASS F INSULATION
IP22 ENCLOSURE
BASLER OR EQUIPMENT VOLTAGE REGULATOR
TWO ANTI-FRICTION BEARINGS
ENGINE:
SUPERIOR MODEL 2416 TURBOCHARGED
4 STROKE CYCLE
NATURAL GAS SPARK IGNITED
1200 RPM, 60 HZ , 1000 RPM 50 HZ
WOODWARD ELECTRONIC GOVERNOR
FUEL GAS INJECTION - EACH CYLINDER
ENGINE DRIVEN LUBRICATING OIL, JACKET WATER AND INTERCOOLER PUMPS
HIGH ENERGY CAPACITOR DISCHARGE IGNITION SYSTEM
INTAKE AIR FILTERS - HEAVY DUTY DRY TYPE
PNEUMATIC STARTING MOTOR
EXHAUST MANIFOLD, WATER COOLED
AUTOMATIC OVERSPEED SHUTDOWN
INTERCOOLER
ENGINE LUBE OIL SUMP
ACCESSORY EQUIPMENT:
LUBRICATING OIL COOLER
LUBRICATING OIL FILTER AND STRAINER
LUBRICATING OIL THERMOSTAT REGULATING VALVE
JACKET WATER THERMOSTAT REGULATING VALVE
JACKET WATER EXPANSION TANK
JACKET WATER RADIATOR
INTERCOOLER SAVER THERMOSTAT REGULATING VALVE
INTERCOOLER WATER RADIATOR
INTERCOOLER WATER EXPANSION TANK
JUNCTION BOXES WITH CONTROL WIRING TERMINATIONS
ENGINE CONTROL PANEL/GAUGE PANEL:
AIR-FUEL CONTROL
ENGINE LUBE OIL PRESSURE GAUGE
ENGINE JACKET WATER TEMPERATURE GAUGE
ENGINE OPERATING TIME METER
INTERCOOLER WATER TEMPERATURE GAUGE
RPM METER
EXHAUST TEMPERATURE METER
ENGINE RDU-DISPLAY UNIT
ENGINE MOUNTED DETECTORS, SWITCHES:
OVERSPEED SWITCH
LOW LUBE OIL PRESSURE SWITCH
HIGH JACKET WATER TEMPERATURE SWITCH
HIGH INTERCOOLER WATER TEMPERATURE SWITCH
LOW STARTING AIR PRESSURE SWITCH
EXHAUST THERMOCOUPLES
LOW OIL LEVELS
LOW WATER LEVEL
A COMMON BASE FOR THE ENGINE, ACCESSORY RACK AND GENERATOR
SWITCHGEAR:
FREESTANDING THREE SECTION GENERATOR SET METAL CLAD MEDIUM VOLTAGE
SWITCHGEAR
TO PROVIDE FOR POWER EXPORT AND UTILITY PARALLELING, USING TWO (2) 20 MW,
II
KV, 3 PHASE, 3W, 50 HZ GENSETS. SWITCHGEAR TO ALLOW FOR REMOTE AUTOSTART,
REMOTE STOP, REMOTE DIAGNOSTIC COMMUNICATION AND AUTO SYNCH WITH UTILITY.
SWITCHGEAR TO ALLOW FOR REMOTE AUTOSTART, REMOTE STOP, REMOTE DIAGNOSTIC
COMMUNICATION AND AUTO SYNCH WITH UTILITY AND WILL INCLUDE:
ONE (1) NEMA 1 ENCLOSURE FOR INDOOR INSTALLATION WITH HINGED FRONT DOORS
APPROXIMATE DIMENSIONS - 95"H X 108"W X 94"D
ONE (1) MAIN HORIZONTAL BUS RATED 1200A 11KV, 5000 MVA AND INCLUDES
1/4" X 2"
|
 |