Home ] Company Info ] Services ] Products ] | Links | Site Map | Contact  [Franηais]

 


In This Section:

Previous
Main 

 

 

 

Solar Taurus 60 

 

Scope of Supply (See below Exhibit A)

Electrical system – NEC Div II 

  • Electrical motors – 380 VAC 50 Hz

  • Space heaters – 220 VAC 60 Hz

Overhauled T7301 Taurus 60 engine – Low hours

Gear Box – 1500 RPM 50 Hz

Generator – Kato 11,000 Vac 4400 kW (nominal) at sea level ISO with no inlet or exhaust losses 

 Start system – AC direct drive

Fuel system – natural gas

Lube oil system

  • Pre/post lube – 120 VDC motor driven

  • Lube oil cooler(s)

  •  Lube oil tank heater – AC 3-phase

Control system

  • Remote two bay PLC with video display terminal  

  • Engineering units - English  

  • Labeling – English  

  • Turbine compressor cleaning – on crank/on-line cleaning  

  • Vibration monitoring – 10 channels, engine, gear box, and generator  

  • Lube oil drain temperature monitoring  

  • Printer logger – 240 VAC 50Hz

  • Electrical metering panel  

  • Supervisory interface – RS232C/422-serial link

  • Synchroscope  

  • Synchronizing system – individual - auto  

  • Motorized voltage adjust

  • Engine performance map and historical display  

  • KW/KVAR controllers  

  •  Generator sequencing – auto start  

  • Generator bearing temperature monitoring  

  • Generator stator windings temp monitoring  

Battery Charger – Nickel cadmium – 120 VDC

Portable turbine wash cart

Prep for domestic shipment

Drawing and manuals

Alignment tool

Testing – engine, generator, package

 Air inlet system

  • Air inlet filter  

  • Air inlet silencer  

  • Air inlet duct  

  •  Air inlet transition elbow  

Exhaust system

  • Ducting – to be determined

Enclosure - Solar standard Taurus Gen Set

  • Electrical system – NEC Div II  

  • Ventilation – Dust protection

  • Reducing elbow vent silencer  

  •  Lighting - 220 Vac  

  • Hi-temp alarm  

Fire suppression / detection system – CO2

  • Fire cylinder cabinet

  Combustible gas monitoring system - dual channel

Turbine handling kit

MCC

Switchgear

Dimensions and weights of each trailer:

  • Turbine Trailer........... 778”L x 103”W x 174”H – 101,390 lbs.

  • PCR Building........... 386”L x 102”W x 119”H –   41,000 lbs.

Price Summary

Sell price for the above scope of supply for:

One (1) Taurus 60 T7301 Continuous Duty Generator Package
:
POA 

Delivery is estimated twelve (12) to fourteen (14) weeks 
Any change to the above scope can effect price and delivery.  
Attached is the standard Refurbishment Work Scope for which the unit was refurbished to.

  Above Pricing does not include:

  • Freight  

  • Field service

  • Agent fees

  • Start up and commissioning  

 

Exhibit A

 Taurus 60

Industrial Power Generation (IPG) gas turbine-generator set

Model No. Taurus 60-7301S
Nominal Output:  5740 kW
Frequency: 50 or 60 available 

Engine

  • Natural Gas Fired

  • Turbotronic Control System, PLC based, 24 vdc

  • 480vac Start Motor (B330) w/ Variable Frequency Drive (VFD430)

  • Lubricating oil system

  • Pneumatically controlled air system

  • SoLoNOx Combustion system

  • Mee Fog Inlet Air System

  • Exhaust Silencer

 Generator

  • 2 Bearing

  • Revolving field

  • 3 phase, AC

  • Drip proof construction with damper windings

  • Direct-connected brushless exciter

  • 12kv output

  • Class F Insulation

  • Automatic Voltage regulator

  • Synchronizing Check relay

  • Voltage ISOCH/DROOP switch

  • Motorized voltage adjustment potentiometer

  • Current and Potential Transformers

  • KVAR/PF Controller

  • Back-up Control relays and Overspeed Monitor

 

Accessories:

  • Drive Gear
    2 stage, epicyclic gear

  • CO2 Fire Suppression System
    With UV & thermal detectors

  • Back-up DC power supply
    96 cells, 120vdc Ni-Cd batteries

  • Vibration Monitoring
    On engine, gear box and generator

Mounted on 2 Semi trailers – each approximately 45’ long, weather tight

 

  NSE Consultants Inc. © 2008 | All Rights Reserved | Top of Page